PRODUCTS

Provided high-quality chemical services for the global coatings, plastics, textiles, construction, agriculture and other fields.

Description

Porcelain insulator is one of the important parts of high voltage transmission and transformation equipment. Because of its strong water absorption on the glazed surface of porcelain bottle, it is easy to use.

Contamination is easy to form conductive film under weather conditions such as rain, fog and dew, resulting in pollution flashover and power failure.

The RJL-AF01 have excellent electrical properties, weather resistance and resistance.           

Temperature and other properties are upgrading products of RTV coatings. 


Technical Index

Typical Physical Properties

Typical properties of the uncured rubber:

Property

DLT   627-2004

Requirement

Value

Appearance

No obvious impurity and   flocculent

No obvious   impurity and flocculent

Tack free time

≤45min(24℃)

32min

Curing time

≤72h(24℃)

49h

Hydrophobicity

Hydrophobic

 

θav≥100°

θmin≥90°

HC:HC1~HC2

θav:117.0°

θmin:104.0°

HC:HC1

Loss of characteristics

 

θav≥90°

θmin≥85°

HC:HC1~HC2

θav:108.4°

θmin:97.2°

HC:HC2

Migration characteristics

 

θav≥110°

θmin≥100°

HC:HC1~HC2

θav:124.6°

θmin:106.7°

HC:HC1

Recovery Time

 

≤24h

<12h

Volume resistivity (Ω.cm)

≥1.0*1014

2.70*1015-2.98*1015

Dielectric constant(100HZ)

εγ≤3.0

2.7-2.8

Dielectric loss

tgδ≤0.3%

0.26-0.29

Dielectric

≥18.0Kv/mm

24.5-25.4Kv/mm

Tracking resistance

≥TMA2.5

TMA4.5

Adhesion

≥grade 2

grade 1

Wear resistance
 

 

≤0.5g

0.2947g

Corrosion resistance
 
Chemical resistance
 

Under acid, alkali, salt,      it should not fall off, Wrinkles,   bubbles, discoloration, etc

Approved

Oil resistance
 
Under insulator, oil,             it should not fall off, wrinkle, bubbles, discoloration

Approved

Power frequency wet flashover voltage comparison
 

 

After coating≥Before coating

After coating=54.5KV

Before coating=50.0KV






Typical properties are only for reference.


Application
This product can be used in variety of applications, including:
Widely used in high-voltage transmission (transformer) electrical equipment (lines) and electric locomotives or porcelain insulators as anti-flashover coatings. It can also be used for transformer equipment, bus bar, motor accessories, transformer, electronic wiring board and communication equipment. Dipping or spraying coating as a moisture-proof and insulation.